Holyoake

7 NOTE Do not fix plaster board to ceiling battens closer that 300mm of the mounting frame. For more detailed instructions please contact your local Holyoake branch. NOTE A flexible plaster product must be used when plastering the diffuser into the ceiling. It is strongly recommended that the joint between the aluminium plaster slot diffuser and the ceiling plaster board is taped with fibre tape prior to plastering. CSDP Mounting Frame - Series CSD-MF Flexible plaster Plaster gauze CSD-MF mounting frame CSDP linear slot diffuser 1 2 CSDP-19 CSDP-25 No. of Slots Diffuser Flange Adapter Size Ceiling Opening Frame Opening Diffuser Flange Adapter Size Ceiling Opening Frame Opening W A H MF W A H MF 1 82 77 107 53 88 83 113 60 2 120 115 145 92 133 127 157 104 3 158 153 183 130 177 172 202 149 4 196 191 221 168 222 216 246 191 CSDP-19 AND CSDP-25 DIMENSIONS CSDP Linear Diffuser (W) CSDP Linear Diffuser Frame opening (MF) CSD-MF Mounting frame CSDA-I Adapter (insulated) (H) Hole size + 5mm Inside adapter size (A) DO NOT fix plaster board to ceiling battens closer than 300mm of mounting frame Ceiling batten Plaster ceiling Screw or rivet CSD-MF Mounting frame Do not bend, crush or damage Ensure plaster board (9-12.5mm) is pushed firmly into tapered slot without distorting mounting frame

RkJQdWJsaXNoZXIy MTI3ODI1